Tulip
* Based on a conductor temperature of :
- 75ºC at 60 hz and the following conditions :
- 32ºC ambient temperature, (1.98 ft/sec - 0.6 m/s) crosswind ( 90º to conductor) ,
- 0.5 coefficient of emissivity, 0.5 coefficient of absorbtivity
- 42º northern lattitude, sea level elevation
- 90º azimut of line ( East-West )
- clear atmosphere and a date and time of noon on July 1( resulting in 95.0 W/ft² of solar and sky radiated heat)
- Actual ampacity will differ basedon local conditions. For specific ampacities, Please contact us.
Tulip
Data sheet
- Cable Name
- Tulip
- AWG ou KCMIL
- 336.4
- Conductors
- A1 (ASC )
- Conducteur Size mm²
- 170.5
- Aluminum - Strandinge no: --- X dia. en '' inches
- 19x0.1331
- O.D. ( ''Inches)
- 0.665
- O.D. ( mm )
- 16.9
- Ampacity 75ºC
- 470
- Break Strength (pounds)
- 6520
- Rated Strength kN
- 29.0