Trillium
  • Trillium

Trillium

* Based on a conductor temperature of :

  • 75ºC at 60 hz and the following conditions :
  • 32ºC ambient temperature, (1.98 ft/sec  - 0.6 m/s) crosswind ( 90º to conductor) ,
  • 0.5 coefficient of emissivity, 0.5 coefficient of absorbtivity
  • 42º northern lattitude, sea level elevation
  • 90º azimut of line ( East-West )
  • clear atmosphere and a date and time of noon on July 1( resulting in 95.0 W/ft² of solar and sky radiated heat)
  • Actual ampacity will differ basedon local conditions. For specific ampacities, Please contact us.

Important: No cables are manufactured or sold here. The specifications of these are used to guide you properly on the types of connectors you may need.

Trillium

Data sheet

Cable Name
Trillium
AWG ou KCMIL
3000.0
Conductors
A1 (ASC )
Conducteur Size mm²
1520.1
Aluminum - Strandinge no: --- X dia. en '' inches
127x0.1537
O.D. ( ''Inches)
1.998
O.D. ( mm )
50.7
Ampacity 75ºC
1705
Break Strength (pounds)
56400
Rated Strength kN
251